Application Note 105U-G-PR2 Profibus Master
Issue 1.2 – May 2005
©ELPRO Technologies Pty Ltd
Page 5 of 13
app_105U-G_PR2_1.2.doc
To assign a new mapping select the “New Fieldbus Mapping” button or to edit it just double click
on the mapping. The write mapping below shows I/O register 4306 with an I/O count of 2 (4306
& 4307) which will be written to Fieldbus I/O location 0. Registers 4306 & 4307 are the Local
Digital Inputs 7 & 8.
The Read mapping shows Fieldbus I/O location 0 with an I/O count of 2 (0& 1) will be read into
Radio I/O registers location 4320 & 4321. Which are the local Digital Outputs 1 & 2.
You can select the button next to the I/O Register box in the Radio Interface to show the available
registers. See below.